Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
IEC898 220V Magnetic Thermal Safety Circuit Breaker 2 Phase Commercial CB
Quick Detail:
Place of Origin: Zhejiang China (Mainland)
Brand Name: JIELI
Model Number: NT-50C
Type: Mini
Poles Number:2
Voltage: 220V
Color: white or black
Current: up to 32A
Standard: IEC898
Description:
The NT-50 Safety Circuit Breaker is used as protection switch for power supply circuit of AC50Hz or 60Hz, voltage 220V, current up to 32A.
NT-50 Safety Circuit Breaker has inherent overload protection function. Combined with a fuse, NT-50 Safety Circuit Breaker can also provide short circuit protection for a circuit.
Besides, NT-50 Safety Circuit Breaker can infrequently make and break a loaded circuit.
NT-50 Safety Circuit Breaker is especially suitable for lighting devices in houses and public places, or a single electric appliance such as refrigerator, etc.
Applications:
NT-50 series safety type Miniature Circuit Breaker features for lively equipment, excellent quality,
beautiful appearance and small volume. NT-50 Safety Circuit Breaker product is suitable for AC 50Hz.
Specifications:
Standard |
IEC 60893 |
|
Number of poles |
2P |
|
Rated current(In) |
6,10,15,20,25,32,40 |
|
Rated voltage(Un) |
AC 240/415V |
|
Rated frequency |
50/60Hz |
|
Tripping curve |
B,C |
|
Release action characteristics |
|
1.13In≥1h non-trip |
1.45In≥1h trip |
||
2.55In 1s60s trip |
||
Instantaneous |
5In≥0.1s non-trip |
|
10In0.1 trip |
||
Magnetic releases operate |
B curve: between 3 and 5In |
|
C curve: between 5 and 10In |
||
Rated breaking capacity(Icn) |
3000A |
|
Endurance |
≥2000 |
|
Circumstance temperature |
-5°C40°C |
|
Electrical life |
≥6000 times |
|
Mechanical life |
10000 times |
|
Tropical ration |
Treat men 2(RH95%,at 55°C) |
|
Protection degree |
IP20 |
China Online UPS Online Market [China (Mainland)]
Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)